hp-Single-pumping unit series MOG
5.0

Single pumping unit for fuel oil in scewed or flanged compact execution, as a feed- or delivery aggregates for oil supply of automatic oil burners - equivalent DIN/EN 4755/2. Produced, tested, registered and marked according to the test standard DIN/EN 12514/1.
Order text:Single pumping unit series MOG
Series MOG: …… Refer to key
Discharge: …… l/h
Medium: ……
Working pressure: …… bar
Motor: …… kW …… V/50 Hz
Accessoires: …… Series key

| Series | Size | Accessories* | |
|---|---|---|---|
| 50 = feed pump aggregate (6 bar and 9 bar), 1)
fuel oil EL + L, Kerosene 51 = feed pump aggregate (9 bar), fuel oil M, S + ES, coaltar oil 52 = delivery aggregate (30 bar), fuel oil EL + L, Kerosene 53 = delivery aggregate 30 bar, fuel oil M, S, + ES 54 = delivery aggregate 40 bar, fuel oil EL + L 55 = delivery aggregate 40 bar, fuel oil M, S + ES |
Discharge see chart | FL = flanged execution | A = pump and filter with electrical stationary heating and connecting box (only for Scheme 1) RV = non-return valve (only for Scheme 2) DK = double ball valve (only for MOG 52 and MOG 54) E1 = with optical filter indicator (only for flanged execution "FL") E2 = with optical and electrical filter indicator (only for flanged execution "FL") LH = oil leakage detection Type HMW S1) = electrical pressure switch for pipe burst monitoring and dry running protection DT = pressure transmitter |
* Listening classification letters after each other
1) For use as feed pump aggregate for the supply with fuel oil per DIN 4736 do not exceed the working pressure of 6 bar.
Note: it is absolutely imperative that the user install an electric pressure switch (acting as a “lower limit controller”), as pipe pressure safety device, on the equipment to which the pump is to be connected. This prerequisite can be met by ordering accessory “S” and “DT”.